Goods warehouse design: racks, forklifts and floor decide the column grid

There is a quick test for any warehouse: stand at the end of a forklift aisle and look down it. If a row of columns stands in the aisle, the building was drawn first and the storage worked out afterwards.

Do it the other way round and the same plot holds more goods. This guide follows that order: goods, racks, forklifts, and only then the building.

Five figures needed before drawing

  • Unit load: size and weight of the pallet or pack, and whether it can be block-stacked.
  • Capacity: pallet positions needed at peak.
  • Rack type: selective, double-deep, drive-in, or block stacking on the floor.
  • Forklift type: counterbalance, reach truck or very narrow aisle truck. Each needs its own aisle width, taken from the truck maker’s data.
  • Throughput: trucks per day and truck type, which give the number of dock doors and the yard area.

The column grid follows the racks

Goods warehouse plan: rack rows, forklift aisles, columns inside rack rows, staging area, dock doors and fire access road
Illustration: plan of a racked goods warehouse. Schematic, not to scale.

One storage module is two back-to-back rack rows plus one aisle. Across the building, column spacing should be a multiple of that module so columns fall inside the rack rows. Along the building, spacing follows a multiple of the rack bay so column bases do not take pallet positions.

Clear height is measured to the lowest item under the roof: rafter underside, fire mains, sprinkler heads, lights. Lose a little here and you lose one rack level across the whole warehouse.

The floor is the most important structure

A leaking roof can be fixed while the warehouse keeps running. A failed floor means clearing the goods and dismantling the racks.

  • Rack leg loads are large point loads on small baseplates. The rack supplier provides the figures; the floor designer checks punching and settlement.
  • Forklift wheel loads repeat many times along the same track.
  • Flatness depends on the truck: high-lift narrow-aisle trucks need a far flatter floor than counterbalance trucks.
  • Joints are set out with the rack grid, kept away from rack legs and, where possible, out of wheel tracks; joint edges are protected.
  • Surface: a hardened, power-trowelled finish for abrasion resistance and low dusting.
  • Ground: a soil investigation is required; on soft ground the floor needs ground improvement or piles.

Loads follow TCVN 2737:2023 and the rack and truck suppliers’ data. For rack-loaded industrial floors, designers commonly also refer to specialist guidance such as Concrete Society TR 34 or ACI 360R.

Dock doors, yard and canopy

  • The floor level above the yard is chosen to suit your most common truck bed; dock levellers take up the remaining difference.
  • The staging area behind the docks is deep enough to marshal one truckload without spilling into rack aisles.
  • The canopy covers the full truck tail; the yard lets container trucks turn and wait.
  • The yard is designed for axle loads, with strengthening where trailer landing legs stand.

Fire protection: decided when the racks are chosen

A warehouse concentrates combustible material. The goods, storage height and floor area decide the fire hazard category, compartment area and required fire-fighting equipment under QCVN 06:2022/BXD with Amendment 1:2023 and TCVN 3890:2023. Automatic water-based systems are designed to TCVN 7336:2021; high racking may also need in-rack sprinklers.

  • The fire water tank and pump room take land and must be on the master plan from the start.
  • Mains and sprinkler heads hang below the rafters: include them in roof loads and clear height.
  • Fire engine access and escape routes affect rack and door positions.
  • The forklift charging area needs ventilation and separation from combustible goods.

This work is done by a qualified fire protection designer and appraised under Law No. 55/2024/QH15 and Decree 105/2025/ND-CP. LLC coordinates so that column grid, height and roof loads match their scheme.

Frame, roof and expansion

Rendering of model LL-X092: long single-storey building with a side loading yard and a two-storey office at one end
Illustration: model LL-X092 with a side loading yard, from LLC’s factory model library.
  • A long-span steel frame with a pitched roof that drains fast; gutters and downpipes sized for heavy rain.
  • Rooflights and lighting follow the aisles, not the rack rows.
  • If rooftop solar is planned, add the load from the start; see rooftop solar on factories.
  • The gable on the expansion side uses a demountable frame and cladding; roads and services are provided for.
  • A mezzanine for piece picking or a warehouse office is best built as an independent steel structure.

What most often has to be redone

  • Columns standing in a forklift aisle.
  • Fire mains lower than the top rack level.
  • A floor joint directly under rack legs.
  • A floor lower than the truck bed, with no dock leveller.
  • No space for the fire water tank.

What LLC does in a goods warehouse

LLC takes the building and structure. Racking, forklifts, dock levellers and fire protection systems come from specialist suppliers.

What to send to get started

The goods and pallet type, positions required, the planned rack and forklift type or the rack supplier’s drawings, trucks per day, a plot plan and the soil report if you have one. Send by Zalo +84 949 021 085 or long.le@thegioinhaxuong.net. Reference prices for building works are on the monthly factory price list. For bagged agricultural produce, see agricultural warehouse design.

Frequently asked questions

How high should a warehouse be?

The height of the loaded top rack level, plus clearance to the sprinkler heads and the rafter underside. Work up from the racks; do not pick the height first.

How thick is a warehouse floor?

There is no standard thickness. The floor is designed for rack leg loads, forklift loads and the ground below; two warehouses of the same area can have very different floors.

Can an old factory become a warehouse?

Yes, after three checks: whether the floor can carry rack loads, whether height and column grid suit the racks, and the fire protection scheme for the change of use.

Sources checked on 26 November 2026: QCVN 06:2022/BXD with Amendment 1:2023 (consolidated text 92/2026/VBHN-TT-BXD, 28 September 2026); TCVN 3890:2023; TCVN 7336:2021; TCVN 2737:2023; TCVN 4317:1986; Law No. 55/2024/QH15 and Decree 105/2025/ND-CP.